Guide

Gas detection in the oil and gas industry: risks, European framework and US references

A practical guide for HSE managers, operators and integrators: which gases to monitor, where and why, and what European texts (legal requirements) and US references (federal requirement, industry practice and recommendations) say. It covers the European Union and the United States; other countries have their own rules.

What is the status of each rule?

SourceStatus
Directives 1999/92/EC and 2014/34/EU (EU)RequirementLegal requirements of the EU, applied through national laws
OSHA, 29 CFR 1910.1000 (United States)RequirementFederal legal requirement (H2S exposure limit)
API RP 54Recommended industry practice: “shall” = minimum requirement of the document, “should” = recommendation
NIOSH, OSHA eTool, MMWR reportRecommendationRecommendations and lessons learned

1Gases and atmospheres at risk

Three hazards combine: the flammability of hydrocarbons, the toxicity of gases such as hydrogen sulfide (H2S), and oxygen deficiency.

H2S is colorless, highly toxic, flammable and heavier than air: it accumulates in low points and confined spaces. The OSHA eTool cites deaths from 700 to 1,000 ppm and near-instant loss of consciousness at 700 ppm and above. NIOSH sets the IDLH value (immediately dangerous to life or health) at 100 ppm and gives a lower explosive limit of 4.0%. The sense of smell tires quickly: it cannot be used to detect a continuous presence of H2S. Combustion produces sulfur dioxide (SO2), which is also toxic.

For hydrocarbon vapors, API RP 54 defines an atmosphere as hazardous notably below 19.5% or above 23.5% oxygen, or above 10% of the lower explosive limit (LEL).

2Where and when the risk arises

  • Drilling and well servicing: H2S may be present. API RP 54 refers to API 49, 55 and 68 for these environments.
  • Flares: H2S and SO2 emissions are possible there (OSHA).
  • Manual tank gauging and sampling: when the hatch is opened, pressure can release a plume of vapors (NIOSH).
  • Confined spaces: API RP 54 provides for an atmospheric test before entry (oxygen, flammable gases, toxic contaminants), then continuous monitoring during occupancy.

3European framework: legal requirements

RequirementDirective 1999/92/EC (worker protection)

Fifteenth individual directive adopted under framework Directive 89/391/EEC. It requires the employer to:

  • take technical and/or organisational measures, in this order: prevent the formation of explosive atmospheres, avoid their ignition, mitigate the harmful effects of an explosion (Art. 3);
  • assess explosion risks (Art. 4) and classify the places concerned into zones (Art. 7, Annex I): zone 0 (explosive atmosphere present continuously, for long periods or frequently), zone 1 (likely to occur occasionally in normal operation), zone 2 (unlikely to occur, and brief if it does);
  • draw up, before work begins, an explosion protection document, kept up to date (Art. 8);
  • provide training, written instructions and work permits where that document requires them (Annex II, Part A);
  • unless the document provides otherwise, select equipment according to the zone (Annex II, Part B): zone 0 → category 1; zone 1 → categories 1 or 2; zone 2 → categories 1, 2 or 3. The annex refers to Directive 94/9/EC, of which Directive 2014/34/EU is the recast.

RequirementDirective 2014/34/EU (equipment)

  • It covers equipment and protective systems intended for use in potentially explosive atmospheres, their components, and certain safety, controlling or regulating devices used outside those atmospheres (Art. 1).
  • Categories 1, 2 and 3 of group II correspond to a very high, high or normal level of protection (Annex I).
  • Whether a given detector falls within its scope depends on its design and use: it is for the manufacturer to specify.

These directives do not mandate a type of detector. They require risk assessment, zoning and suitable equipment. National laws may detail the transposition.

4US references

RequirementFederal legal requirement

For H2S in general industry, OSHA sets a ceiling of 20 ppm. A peak of up to 50 ppm is tolerated for 10 minutes at most, only if there is no other measurable H2S exposure during the eight-hour workday. In construction and shipyards, the limit is an average of 10 ppm.

RecommendationRecommendations

  • NIOSH recommends a ceiling of 10 ppm over 10 minutes.
  • The OSHA eTool describes 10 ppm as an alarm threshold commonly used by industry.
  • The eTool also recommends personal and area monitoring, a personal detector placed near the breathing zone, and calibration and maintenance according to the manufacturer.
  • The eTool states that a detector alone is not enough against near-instant collapse at high concentration.
  • For hydrocarbon vapors, NIOSH recommends calibrated multigas detectors (LEL and oxygen).

Industry practice

API RP 54 (4th edition, February 2019) is a recommended practice: whether it is binding depends on its adoption by a regulator or a contract.

5Operation and good practice

  • Test the atmosphere before entering a confined space, then monitor continuously (API RP 54).
  • Calibrate and maintain detectors, and know how to respond to alarms (OSHA eTool, NIOSH).
  • Avoid working alone in at-risk areas (NIOSH).
  • Use suitable respiratory protection: filtering respirators do not protect against ethane, propane and butane, or in oxygen-deficient atmospheres (NIOSH). API RP 54 provides for self-contained or supplied-air breathing apparatus when tests reveal toxic gases at IDLH level or insufficient oxygen.

6Lessons learned: manual tank gauging

The MMWR report of 15 January 2016 records 9 deaths of oil and gas extraction workers, from January 2010 to March 2015.

Facts documented in the report

  • 5 deaths during fluid sampling and 4 during manual tank gauging.
  • All the workers were alone.
  • Measurements available in two cases: about 11% oxygen near the tank opening, with hydrocarbon gases and vapors above the LEL, and 7% oxygen in another case.
  • Only one worker in nine wore a respirator, and it was not suited to these concentrations.

Suspected factors, not established case by case

  • A link between the deaths and exposure to hydrocarbon gases and vapors and to oxygen deficiency, retained by the report as the probable cause.
  • A mechanism of sudden cardiac death at very high concentration (above 100,000 ppm), notably with pre-existing coronary disease: death certificates mention cardiovascular diseases.
  • The NIOSH post on the first cases rules out H2S as a cause.

RecommendationNIOSH recommendation

Replace manual gauging with electronic systems (sonar, in-line flow meters) or, failing that, limit manual gauging by procedure.